Motor circuit troubleshooting trainer

A three-wire starter with a hidden fault and a voltmeter: place your leads, work the panel, and name the fault.

Result

Voltmeter · AC

— · —

Click a test point for the red lead, another for the black. After both are set, new clicks walk the red lead; click a lead to lift it.

No calls yet — measure first, then name it below the diagram.

POWER · 480 V 3φF1F2F3M · outOL heatersMstoppedCPT · 480 → 120 Vfeeds X1 / X2 belowCONTROL · 120 V — wire numbers as markedCFSTOPSTARTM auxMcoilOL1234L1L2L3LF1LF2LF3X1X2

Call it — what is the fault?

Formula sources: Half-split voltage troubleshooting on series control circuits (standard motor-controls lab method), Simplified readings: fuse checks shown at nominal line voltage; ghost/backfeed readings noted where they matter

A training simulator — a real starter cabinet is live at 480 V. Lockout/tagout before opening, verify dead with a meter you've tested on a known source, and treat every backfed reading as live equipment. Never bypass a safety device to make a machine run.