PLC signal scaling

Convert between wire signal, raw ADC counts and engineering units — plus the slope and offset for your scaling block.

Result

75 PSI
= 12 mA = 13824 counts · 50% of span
Scaling blockEU = 0.005425 · raw + 0
Resolution0.005425 PSI per count

4–20 mA carries a live zero: 4 mA means 'measuring zero', 0 mA means 'the loop is broken' — the reason current loops rule industrial floors.

One line, three rulers
Signal (mA)42012Raw counts02764813824PSI015075

Formula sources: Linear interpolation across signal, raw, and engineering-unit spans, NAMUR NE43 — fault signaling below 3.6 mA on 4–20 mA loops

Exact linear scaling — but raw count ranges vary by card and configuration. Verify min/max against your module's datasheet before commissioning; this is a reference instrument, not a substitute for loop checkout.